Xuất xứ: EU
Model: RD-30
Cấp chính xác: +/- 0.04
Hãng Radian Research
| General | ||||||
| Operating Range: | 
 | |||||
| PF Accuracy | Power Factor | RD-30 | RD-31 | RD-33 | 
| > 0.5 | 0.04 % | 0.02 % | 0.01 % | |
| 
 | 0.04 %/2PF | 0.02 %/2PF | 0.01 %/2PF | 
| 
 | Harmonic Analysis: < 64th (bandwidth 10000 Hz) | 
| Dimensions: | 5″(127 mm), 17.5″ (444.5 mm), 6.25″ (158.7 mm) | 
| Weight: | 16 lbs (7.2 kg), Shipping weight 28 lbs (12.6 kg) | 
| Environment:. | Operating & Storage Temp: -20°C to +70°C | 
| 
 | Humidity: 0 % to 95 % non condensing | 
| 
 | Vibration: All non destructive | 
| Safety: | Hi-Pot: 2.3 kVrms, 60 Hz for 60 seconds | 
| 
 | Surge: IEEE 472 and ANSI 37.90 | 
| 
 | Fused: Potential and Auxiliary Input | 
| Warm-up: | 15 seconds | 
| Interface | |
| Display: | Touch screen, color back lit LCD | 
| Communications: | Serial Port: RS -232 | 
| 
 | Sensor Port: Lemo type | 
| 
 | Clamp Probe Port: 3 CT Inputs (optional Clamps from Radian) | 
| Inputs 1,2 & 3: | BNC Display gate: 150 Ohm pull up to 5 V, clamped at 5.7 V | 
| 
 | BNC Gate rate: 200 nS pulse width minimum, maximum 20 Hz repetition rate. | 
| Outputs 1, 2 & 3: (default = 0.00001 Wh/pulse) | Programmable KH value Open collector, clamped at 27 V Max 2.1 MHz (200nS pulse width minimum) Selectable Watt Hours, VAR Hours, VA Hours | 
| 
 | Current Inputs: 6 mm (<120 Amp), 8 mm (<200 Amp option) | 
| 
 | Aux & Potential Inputs: 4 mm | 
| Specifications | |||||||||
| Function | Reading | Accuracy (ppm)3 | Stability | Cal Unc. | Temperature Coefficient6 (ppm/°C) | ||||
| RD-30 | RD-31 | RD-33 | RD-30 | RD-31 | RD-33 | ||||
| Voltage | 30 V to 630 V5 | 200 | 100 | 50 | 8 | 4 | 2 | 30 | 2.5 | 
| Current | 1 mA … 10 mA2 | 280 | 140 | 70 | 12 | 6 | 3 | 50 | 2.5 | 
| 10 mA … 200 A | |||||||||
| Power/Energy 3,4 | 1 mA … 10 mA2 | 400 | 200 | 100 | 16 | 8 | 4 | 80 | 5 | 
| 10 mA … 200 A | |||||||||
| Power Factor | > 0.5 | 0.04 % | 0.02 % | 0.01 % | |||||
| 
 | 0.04%/2PF | 0.02%/2PF | 0.01%/2PF | ||||||
| Phase angle | 0° … 360° | 0.012° | 0.006° | 0.003° | |||||
| RD-BR1 CT Burden & Ratio Analysis Specifications | ||
| Input Power | RD Standard connection (Allows 60-600V at Site) | |
| Measurement Inputs | Primary CT Current: | 0.1 – 3000 Amperes, 50 or 60 Hz (using probes) | 
| Secondary CT Current: | 0.01 – 20 Amperes, 50 or 60 Hz | |
| CT Primary Probe Input Voltage: | 3V RMS Max (using RR-CTA1) | |
| Probe Scales: | 10mV/A | |
| Accuracy | Dependent on RD standard & clamp-on probe selected | |
| CT Burden Testing | CT Burden Value: | 0.1, 0.2, 0.5, 1.0,4.0 & 8.0 Ohms | 
| Resistive Element Tolerance: | +/- 1% | |
| Insertion Burden: | +/- 0.04 Ohms | |



 0913457887
 0913457887 0.5